Raylux 2026.24: Alarms, Security and Devices and drivers
Raylux 2026.24 adds alarm shelving, two-step sign-in for local accounts, and a way to find the devices on your network and add them in a few clicks. It also fixes alarm pipelines, reports and configuration pages that did not do what they showed, and adds Raylux Edge Panel.
Raylux 2026.24 adds alarm shelving, two-step sign-in for local accounts, and a way to find the devices on your network and add them in a few clicks. It also fixes alarm pipelines, reports and configuration pages that did not do what they showed, and adds Raylux Edge Panel.
Does this affect me?
- Upgrading a running gateway: install over 2026.23 as usual. Projects, tags, history, users and alarm configuration are kept, and nothing in this release needs a gateway restart to configure.
- Two-step sign-in is off until you turn it on. Nobody is asked for a code after upgrading. Accounts that sign in through your identity provider are not affected; set up two-step sign-in there.
- Alarm pipelines may start doing more after the upgrade. Delay, set-property, script, switch and expression steps drawn in the designer were being skipped or run with no delay. They now run as drawn, with no need to re-save the pipeline. Check pipelines you built expecting those steps to do nothing.
- Configuration pages save what they show. Historian retention and flush interval now stick. A few fields that never did anything (historian backend, pool size, query timeout, device retry count) are removed. Connection defaults on the Devices and OPC UA pages now apply to every connection that does not set its own value. Values left there by earlier versions change nothing until you save them again.
- Update queries no longer run from screen bindings. A named query that changes data (INSERT, UPDATE or DELETE) bound to a component property is refused and shows a binding error, so it can no longer re-run on every refresh. Buttons and scripts that run update queries work as before.
- History records without a named connection. A tag with history turned on and no historian connection chosen now records to the built-in historian. Before, it was silently dropped.
- Hidden components in a flex layout no longer leave a gap where they would be.
Alarms
- Alarm shelving. Shelve an active alarm for 1 minute up to 24 hours, with a required reason. A shelved alarm keeps evaluating, but it leaves the active list, the counts and notifications until the shelf ends on its own or someone ends it. Shelves survive a gateway restart, and every shelve is logged in the audit trail. The Alarm Table gets a Shelve button and a shelved count, both of which can be turned off. Shelving needs tag write access and a signed-in user.
- Alarm pipelines run the way they are drawn.
- Delay steps wait for the time you set.
- Set-property steps write their tag, converted to the tag's type, and refuse values out of range.
- Script steps run, with the alarm available to the script, and are stopped after 5 seconds.
- Switch and expression steps evaluate their conditions.
- A notification step sends its own message when it has one, at every stage of the escalation.
- Webhook steps are not active yet. They arrive in a later release.
Security
- Two-step sign-in for local accounts. Users enroll an authenticator app by scanning a QR code and get 10 single-use recovery codes. An administrator can require it for every local account, live, and can reset a user who lost their phone (the reset is audited). It works in the browser sign-in, the plant-floor client and the designer. Wrong codes count toward the sign-in lockout. Kiosks that run without signing in are unaffected.
Devices and drivers
- Find devices. Devices › Find devices looks for EtherNet/IP and BACnet/IP devices on the network, and for Modbus TCP devices in an address range you enter (up to 256 addresses). Tick the ones you want and add them in one step, or review each one in the Add form first. Allen-Bradley controllers are given their PLC type from their catalog number where it is clear (ControlLogix, CompactLogix, Micro800), and you can change it. A new gateway with no devices shows a banner pointing to it; an upgraded gateway that already has devices does not. Every scan is logged in the audit trail.
- Unreachable devices no longer stall the gateway. DNP3, Modbus TCP, Siemens S7 and Omron connections give up after the device's own timeout instead of waiting about two minutes. Stopping the gateway with an unreachable DNP3 outstation went from 142 seconds to under 2.
- Device tag import reads type suffixes. An address such as
HR100:float32orIR30:uint16sets the tag's data type and keeps the suffix out of the tag name. An unknown suffix is refused on that row with a message. - The DNP3 select timeout now saves.
- Connection status tags. Each device connection publishes whether it is connected and when it last communicated, under
[SYSTEM]Devices/<name>/, live.
History and reports
- Time-weighted average and integral. History queries can return a time-weighted average or an integral (energy in kWh from a kW tag, for example), and can ask for today or this month. This works in bindings, scripts and the REST API.
- Report parameters reach your queries, in every report format, and override a named query's own default. Values are always passed as parameters, never pasted into the SQL.
- Scheduled reports fetch every data source, named queries and tags included.
- Dates in report text format the way you ask.
dateFormat()andformat()take a date pattern and the time zone of your choice. - A report's named query uses its own database connection.
Designer and runtime
- Page URLs can carry values. A page route such as
/circuit/:idpassesidto the page, and navigation actions fill it in. One page can serve every circuit, tank or line. - Open screens follow a project's update setting when it changes. Switching a project from "notify" to "automatic" updates reaches plant-floor screens that are already open at the next save, with no tap needed.
- More color properties. Alarm Table, Moving Analog Indicator, Text Input, Multistate Button and Progress Bar get color properties you can set in the designer or from style classes. A component left at its defaults looks the same as before.
- Style classes bound on a screen work. A style class bound on a page, popup, dock or embedded view now applies and updates live.
- Dim quality marking. Every component can show bad or stale quality as a dimmed value instead of the standard marking.
- New component: Heat Trace Line. A live isometric drawing of a pipe run with its heat trace cable state and temperature, including buried sections, valves, strainers and reducers. Pipes that cross are drawn the way a drafter would, and the drawing turns itself to keep pipes from overlapping.
- The bare
/runtimeaddress opens the gateway's only project, or the list when there are several.
Raylux Edge Panel
- Edge Panel installers. The Windows installer and the Linux packages can set a panel PC up as a Raylux Edge Panel: the gateway plus a full-screen operator display that starts with the machine. On Linux the boot-to-display service is installed turned off, for you to enable.
- Edge licenses do not limit tags, devices, users or projects. Only operator sessions and history length are capped.
- The panel's browser no longer asks to create a keyring at every start on desktop Linux images.
Downloads
- RayluxSetup-2026.24-x64.exe: the whole system for Windows (gateway, designer and plant-floor client). Start here if you are not sure.
- Raylux-2026.24-x64.msi: the gateway on its own for Windows, for scripted or unattended installs.
- Raylux-Studio-Setup-2026.24-x64.exe: the designer, for an engineer's workstation.
- Raylux-Lens-Setup-2026.24-x64.exe: the plant-floor client, for operator stations.
- raylux-nexus_2026.24_amd64.deb: the gateway for Debian and Ubuntu on x86-64:
sudo apt install ./raylux-nexus_2026.24_amd64.deb - raylux-nexus-2026.24-1.x86_64.rpm: the gateway for Fedora and RHEL on x86-64:
sudo dnf install ./raylux-nexus-2026.24-1.x86_64.rpm - raylux-nexus_2026.24_arm64.deb: the gateway for ARM64 boards and panels on Debian, Ubuntu or Raspberry Pi OS (64-bit):
sudo apt install ./raylux-nexus_2026.24_arm64.deb - raylux-nexus-2026.24-1.aarch64.rpm: the gateway for ARM64 Fedora and RHEL:
sudo dnf install ./raylux-nexus-2026.24-1.aarch64.rpm
The Windows installers need 64-bit Windows 10 or 11, or Windows Server 2019 or later. They are not code-signed yet, so Windows may warn before running them; check the SHA-256 checksum on the downloads page first.
The Linux packages, x86-64 and ARM64, need glibc 2.38 or later: Ubuntu 24.04, Debian 13, Raspberry Pi OS based on Debian 13, Fedora 39 or later.
Next step
Run the latest release.
Every 1.0 release installs over the one before it and keeps your projects, tags, history and users. Follow new ones in a feed reader, no email needed.